1250kVA Dry Type Transformer

Specify a 1250kVA dry type transformer for indoor power rooms, commercial buildings, industrial feeders and EPC distribution packages. This page summarizes the key electrical and procurement data needed before quotation.

Send RFQDownload Datasheet
1250kVA Dry Type Transformer

Rated Capacity

1250kVA

Transformer Type

Cast-resin dry type distribution transformer

Typical Voltage

10kV primary with 0.4kV secondary; 11kV, 22kV or 33kV by project design

Cooling

AN standard, AF optional by project requirement

Product Overview

Engineering Selection Context

A 1250kVA dry type transformer is commonly selected where fire safety, low routine maintenance and indoor installation are more important than the lowest initial price. It can be configured for distribution rooms, package substations, hospitals, data rooms, commercial towers and factory workshops.

This page sits inside ZY POWER's SCB13, SCB14 and SCB18 cast-resin dry type transformer family. The full dry type portfolio covers 30-3,150kVA; this landing page focuses on the 1250kVA selection point used in building and industrial distribution schedules.

For procurement, the capacity alone is not enough. The RFQ should also state primary voltage, secondary voltage, frequency, vector group, impedance, enclosure rating, temperature controller requirement, fan option and site altitude.

Ziyao Power supplies project-specific dry type transformer proposals based on IEC and local tender requirements, with drawings, datasheets and test documents prepared for engineering approval.

Technical Specifications

Key Data Required Before Quotation

These values should be confirmed against the single-line diagram, tender document and site conditions.

Rated Capacity1250kVA
Product FamilySCB13, SCB14 or SCB18 cast-resin dry type transformer
Rated Voltage10/0.4kV standard reference; 11/0.4kV, 22/0.4kV or 33/0.4kV by project-defined ratio
Frequency50Hz or 60Hz
PhaseThree phase
Vector GroupDyn11 or specified by project design
Cooling MethodAN, with AF fan cooling optional
Insulation ClassClass F or Class H insulation system
Efficiency OptionSCB13 Class 3, SCB14 Class 2, SCB18 Class 1 under GB 20052-2020 where specified
Protection LevelIP00 for indoor cabinet integration, IP20/IP23/IP31 enclosure optional
Installation TypeIndoor floor-mounted transformer room, package substation or switchgear room
StandardIEC 60076 series, IEC 60076-11, GB/T 10228, GB 20052-2020 or tender-specified standard

Construction & Materials

Build Details Buyers Should Confirm

Material decisions influence loss level, thermal behavior, footprint, maintenance and approval documents.

High-grade silicon steel core with low-loss magnetic design for distribution service; amorphous alloy wording is reserved for SH15/SBH15/SCBH15 series, not SCB dry type pages.

Epoxy cast-resin HV windings for moisture resistance, mechanical strength and fire-safe indoor operation.

Copper or aluminum windings selected according to tender budget, loss requirement and project preference.

Temperature monitoring terminals, PT100 sensor option and fan control interface for transformer room supervision.

Sheet steel protective enclosure optional when the transformer is installed in public, dusty or high-touch areas.

Applications

Where This Page Fits

Commercial building main distribution rooms and shopping centers.

Hospitals, schools, data rooms and other indoor low-fire-risk projects.

Factory workshops, process lines and industrial power distribution feeders.

PV, battery storage and microgrid auxiliary distribution systems.

Package substation and switchgear room integration where oil equipment is not preferred.

Standards & Compliance

Documents for Engineering Review

IEC 60076 power transformer general requirements.

IEC 60076-11 dry type transformer requirements and tests.

Routine tests such as winding resistance, voltage ratio, vector group, insulation resistance and applied voltage test.

Project documents can include outline drawing, wiring diagram, test report, nameplate and packing list.

FAQ

Procurement Questions

What information is needed to quote a 1250kVA dry type transformer?

Please provide capacity 1250kVA, primary and secondary voltage, frequency, vector group, impedance, cooling method, enclosure IP rating, winding material preference and destination country.

Can a 1250kVA dry type transformer be used indoors?

Yes. Dry type transformers are commonly used indoors because they do not use mineral oil and can be installed in transformer rooms with suitable ventilation and clearance.

Should I choose copper or aluminum windings?

Copper is often preferred for compact design and lower resistance, while aluminum can be used when the project prioritizes cost. The final choice should match tender requirements and loss targets.

Should I choose SCB13, SCB14 or SCB18?

SCB13 is a cost-effective standard dry type option, SCB14 is the middle efficiency step, and SCB18 is the GB 20052-2020 Class-1 efficiency option. SCB18 is usually preferred for data centers, hospitals, green-building projects and owner-operated sites with long operating hours.

Is AN cooling enough for this capacity?

AN cooling is the standard natural-air option. AF fan cooling can be specified when the project requires temporary overload margin or improved heat removal.

What enclosure rating should be selected?

IP00 is suitable inside locked transformer rooms or cabinets. IP20, IP23 or IP31 enclosures are used when touch protection, dust protection or public-area safety is required.

Does the transformer need a temperature controller?

A temperature controller is recommended for dry type transformers so alarm, trip and fan control signals can be integrated with the building or plant electrical system.

Can the voltage ratio be customized?

Yes. Common ratios include 10/0.4kV, 11/0.4kV, 22/0.4kV and 33/0.4kV, but the final ratio should follow the utility connection and low-voltage distribution design.

What documents are supplied after order confirmation?

Typical documents include outline drawing, technical datasheet, test report, nameplate, packing list and operation notes required for engineering approval.

How should I compare two transformer quotations?

Compare voltage ratio, energy-efficiency class, no-load and load loss, winding material, insulation class, cooling method, enclosure, accessories, test scope, drawings, delivery terms and warranty, not only the unit price.

RFQ CTA

Send your specification for engineering review

Attach a transformer schedule, single-line diagram, switchgear drawing or load list. Our team will match the product configuration to voltage, capacity, installation and approval requirements.

Request Quotation

Related Products

Continue Product Selection

SCB13 Dry Type Transformer

Cast-resin distribution transformer for indoor power rooms and commercial buildings.

View product

SCB14 Dry Type Transformer

Higher-efficiency dry type transformer option for long operating hours.

View product

Power Transformers

Dry type, oil immersed and amorphous alloy transformer systems.

View product

Downloads

Transformer Selection GuideUse the selection guide to prepare voltage ratio, capacity, impedance and enclosure notes before RFQ.SCB13 Dry Type DatasheetReference dry type transformer datasheet for engineering review.

Related Technical Articles

Dry-Type Transformer Selection GuideSelection notes for epoxy cast-resin dry type transformers.SCB13 Transformer Selection GuideRFQ checklist and engineering selection factors for SCB13 series.Transformer BasicsCore transformer sizing, voltage and cooling concepts.

Products

  • Power Transformers
  • Substations
  • Medium Voltage Switchgear
  • Low Voltage Switchgear
  • Circuit Breakers
  • Instrument Transformers
  • Power Cables
  • Renewable Energy Solutions
  • Metering Solutions

Solutions

  • Power Generation
  • Industrial Plants
  • Utility Distribution
  • Renewable Energy

Support

  • Downloads
  • Knowledge Center
  • FAQ
  • Inquiry

Company

  • Company Profile
  • Factory Tour
  • Projects
  • Contact

Contact

  • sales@ziyaopower.com
  • WhatsApp: +86 151 5609 3235
  • +86 151 5609 3235
  • LinkedIn

Copyright 2026 ZY POWER. All rights reserved.

Zhejiang, China